3 Core + Earth (4G), 2.5mm, 0.6/1KV, PVC 90°C, SWA, Industrial Power Cable (MASCP4G/2.5SWA)

APPLICATION:
Suitable for Mains and Submains where Mechanical Protection is required.
Suitable for Direct Burial and Outdoor Installations.

Standards AS/NZS1125, AS/NZS3008, AS/NZS3808, AS/NZS5000.1, IEC60332-1-2, AS/NZS60079.14, RoHS Compliant
Voltage 0.6/1KV
Nominal Amps Unenclosed 25 Amps
Nominal Amps Buried Direct in Ground 28 Amps
Max. D.C Resistance @ 20°C (Ω/KM) 7.41
Conductor Stranded Tinned Copper Conductor
Insulation PVC V90
Core Colours Red, White, Blue, Green/Yellow
Separator PET Tape or Non-Woven Tape
Bedding PVC , 5V-90 , Flame Retardant
UV Resistant Black PVC
Armour Galvanised Steel Wire
Sheath SPVC , 5V-90 , Black
Operating Temp. -20°C to +90°C
Bending Radius (Fixed) 12D (D = Cable Diameter)

Additional information

No. of Conductors

3 Core + Earth

Nominal Area

2.5mm²

Stranding No./Size

7/0.67+7/0.67

Armouring

SWA

sdoc-mascc-mascp-mascpx-1
Number of Cores / SizeConductor Size (mm²)Conductor StrandingInsulation Thickness (mm)Sheath Thickness (mm)Armour Wire Diameter (mm)Approx. Cable O.D (mm)Approx. Cable Weight (Kg/Km)Maser CodeDownload Datasheet
2x10.0+E4.010.0mm7/1.35+7/0.850.71.81.2519.9803MASCPX3G/10.0SWADatasheet
2x16.0+E6.016.0mm7/1.70+7/1.040.71.81.2521.91014MASCPX3G/16.0SWADatasheet
2x25.0+E6.025.0mm19/1.35+7/1.040.9/0.71.81.625.81464MASCPX3G/25.0SWADatasheet
3x10.0+E4.010.0mm7/1.35+7/0.850.71.81.2521.3955MASCPX4G/10.0SWADatasheet
3x16.0+E6.016.0mm7/1.70+7/1.040.71.81.2523.51226MASCPX4G/16.0SWADatasheet
3x25.0+E6.025.0mm19/1.35+7/1.040.9/0.71.81.627.11749MASCPX4G/25.0SWADatasheet
3x35.0+E10.035.0mm19/1.53+7/1.350.9/.071.81.629.42166MASCPX4G/35.0SWADatasheet
3x50.0+E16.050.0mm19/1.83+7/1.701.0/0.71.91.632.92813MASCPX4G/50.0SWADatasheet
3x70.0+E25.070.0mm19/2.14+19/1.351.1/0.92.1238.94002MASCPX4G/70.0SWADatasheet
3x95.0+E25.095.0mm37/1.78+19/1.351.1/0.92.22424865MASCPX4G/95.0SWADatasheet
4x10.0+E4.010.0mm7/1.35+7/0.850.71.81.2522.91123MASCPX5G/10.0SWADatasheet
4x16.0+E6.016.0mm7/1.70+7/1.040.71.81.6261603MASCPX5G/16.0SWADatasheet
4x25.0+E6.025.0mm19/1.35+7/1.040.9/0.71.81.629.52114MASCPX5G/25.0SWADatasheet
4x35.0+E10.035.0mm19/1.53+7/1.350.9/0.71.91.632.32656MASCPX5G/35.0SWADatasheet
4x50.0+E16.050.0mm19/1.83+7/1.701.0/0.72237.43756MASCPX5G/50.0SWADatasheet
4x70.0+E25.070.0mm19/2.14+19/1.351.1/0.092.2243.34978MASCPX5G/70.0SWADatasheet
4x95.0+E25.095.0mm37/1.78+19/1.351.1/0.92.3246.96110MASCPX5G/95.0SWADatasheet

 

Physical Characteristics 
ConductorStranded Tinned Copper Conductor
InsulationXLPE X-90
Core Colours2C+E (3G) Red, Black, Green/Yellow
3C+E (4G) Red, White, Blue, Green/Yellow
4C+E (5G) Red, White, Blue, Black, Green/Yellow
SeparatorPET Tape or Non-Woven Tape
Sheath PVC, 5V-90, Black
Bending Radius (Fixed)12D (D = Cable Diameter)
ArmourGalvanised Steel Wire
Sheath PVC, 5V-90, Flame Retardant, UV Resistant Black PVC
Operating Temp.-20°C to +90°C
Electrical Characteristics
Voltage0.6/1KV
StandardsAS/NZS1125 , AS/NZS3008 , AS/NZS3808 , AS/NZS5000.1 , IEC60332-1-2 , IEC60332-3-22 AS/NZS60079.14 , RoHS Compliant

 

Electrical Characteristics    
Conductor Size (mm²)Nominal Amps
Unenclosed, Fixed, Touching
Nominal Amps Buried Direct in groundMax. D.C. Resistance @ 20°C (Ω/KM)3 Phase Voltage Drop (@ 50Hz & 90°C) mV/A.m
10.0mm68 Amps67 Amps1.834.05
16.0mm91 Amps118 Amps1.152.55
25.0mm122 Amps153 Amps0.7271.61
35.0mm151 Amps184 Amps0.5241.17
50.0mm185 Amps218 Amps0.3870.868
70.0mm234 Amps269 Amps0.2680.609
95.0mm289 Amps322 Amps0.1770.45

 

Number of Cores / SizeConductor Size (mm²)Conductor StrandingInsulation Thickness (mm)Sheath Thickness (mm)Armour Wire Diameter (mm)Approx. Cable O.D (mm)Approx. Cable Weight (Kg/Km)Maser CodeDownload Datasheet
2x1.5+E1.51.5mm7/0.50+7/0.500.81.80.914.4373MASCP3G/1.5SWADatasheet
2x2.5+E2.52.5mm7/0.67+7/0.670.81.80.915.4437MASCP3G/2.5SWADatasheet
2x4.0+E2.54.0mm7/0.85+7/0.671.0/0.81.80.916.8518MASCP3G/4.0SWADatasheet
2x6.0+E2.56.0mm7/1.04+7/0.671.0/0.81.81.2518.5711MASCP3G/6.0SWADatasheet
3x1.5+E1.51.5mm7/0.50+7/0.500.81.80.915.2420MASCP4G/1.5SWADatasheet
3x2.5+E2.52.5mm7/0.67+7/0.670.81.80.916.3498MASCP4G/2.5SWADatasheet
3x4.0+E2.54.0mm7/0.85+7/0.671.0/0.81.81.2518.9738MASCP4G/4.0SWADatasheet
3x6.0+E2.56.0mm7/1.04+7/0.671.0/0.81.81.2520842MASCP4G/6.0SWADatasheet
4x1.5+E1.51.5mm7/0.50+7/0.500.81.80.916.1462MASCP5G/1.5SWADatasheet
4x2.5+E2.52.5mm7/0.67+7/0.670.81.80.917.3554MASCP5G/2.5SWADatasheet
4x4.0+E2.54.0mm7/0.85+7/0.671.0/0.81.81.2520.3829MASCP5G/4.0SWADatasheet
4x6.0+E2.56.0mm7/1.04+7/0.671.0/0.81.81.2521.6959MASCP5G/6.0SWADatasheet
Physical Characteristics 
ConductorStranded Tinned Copper Conductor
InsulationPVC, V90
Core Colours2C+E (3G) Red, Black, Green/Yellow
3C+E (4G) Red, White, Blue, Green/Yellow
4C+E (5G) Red, White, Blue, Black, Green/Yellow
SeparatorPET Tape or Non-Woven Tape
Sheath SPVC , 5V-90 , Black
Bending Radius (Fixed)12D (D = Cable Diameter)
ArmourGalvanised Steel Wire
Sheath PVC, 5V-90, Flame Retardant, UV Resistant Black PVC
Operating Temp.-20°C to +90°C
Electrical Characteristics
Voltage0.6/1KV
Standards: AS/NZS1125 , AS/NZS3008 , AS/NZS3808 , AS/NZS5000.1 , IEC60332-1-2 , IEC60332-3-22 AS/NZS60079.14 , RoHS Compliant
Conductor Size (mm²)Nominal Amps Unenclosed, Fixed, TouchingNominal Amps Buried Direct in groundMax. D.C. Resistance @ 20°C (Ω/KM)3 Phase Voltage Drop (@ 50Hz & 90°C) mV/A.m
1.5mm17 Amps20 Amps13.630
2.5mm25 Amps28 Amps7.4116.4
4.0mm33 Amps36 Amps4.6110.2
6.0mm42 Amps46 Amps3.086.8

 

http://www.goactive.net.nz/find-your-nearest-electrical-supplier/http://www.advanceelectrical.co.nz/store-locations.htmlhttps://www.corys.co.nz/about/findhttp://www.ideal.co.nz/contact/brancheshttp://www.iesltd.co.nz/contact.htmlhttp://www.jarussell.co.nz/find-a-branchhttp://www.jarussell.co.nz/find-a-branchhttp://www.redpaths.co.nz/about-us/branch-locations/http://www.scottelectrical.co.nz/find-us.htmlhttp://www.telfers.co.nz/